Skip to content
Fleks

Guide · 4 min read

Polyamide vs PVC corrugated conduit: the difference

Fleks Elektrik Technical Team

In short

Polyamide corrugated conduit works from −40 °C to +120 °C, is halogen-free and self-extinguishing. PVC corrugated conduit works from −20 °C to +70 °C and is made for general-purpose installations. Polyamide is chosen where it is hot, where things move, or where halogen-free material is required.

The short answer

Polyamide (PA6) corrugated conduit is for machine wiring, moving equipment and hot spots; PVC corrugated conduit is for general-purpose electrical installations. Both are highly flexible and rated IP66–IP68; they differ in temperature, in fire behaviour and in whether the material contains halogens.

Comparison table

FeaturePolyamide (PA6) conduitPVC corrugated conduit
Operating temperature−40 °C / +120 °C−20 °C / +70 °C
Flammability classUL94 V2, self-extinguishingUL94 HB
HalogensHalogen-freeHalogenated (PVC)
Protection classIP66–IP68IP66–IP68
Mechanical dataBending radius 15–90 mmCompression 450 N, tensile 250 N
SizesØ10–54.4 mm, 13 sizesØ8–50 mm, 16 sizes
ColoursGrey (RAL 7031), black (RAL 9011)Grey (RAL 7031), black (RAL 9011)
Coils100, 50 and 25 m30 m

The sizes in the table are outer diameters. Polyamide conduit goes by NW size: NW 17, for example, is 16.8 mm inside and 21.4 mm outside. For PVC corrugated conduit the nominal size equals the inner diameter: size 20 is 20 mm inside and 24.7 mm outside.

Temperature and fire behaviour

Polyamide withstands up to +120 °C; near motors, heaters and hot machine parts, the +70 °C limit of PVC may not be enough. Fire behaviour differs too: polyamide is rated UL94 V2 and is self-extinguishing, while PVC corrugated conduit is rated UL94 HB. Being halogen-free, polyamide gives off no halogen gases in a fire, which is decisive in enclosed spaces and on projects that require halogen-free material.

Movement and flexibility

Polyamide conduit is light and highly flexible; it protects cables in machine wiring and on moving equipment. Its bending radius runs from 15 mm to 90 mm depending on size. To protect a cable bundle already in place without disconnecting it, use the Split Polyamide Corrugated Conduit, slit along its length, in the same material and sizes.

Connectors and accessories

Polyamide conduit forms a complete system with Polyamide Conduit Connectors & Accessories: straight and 90° elbow connectors, compression connectors, capped clips, and Y and T distributors. The connectors seal to IP67 with a suitable gasket and come with metric and PG threads; the metric types come with a lock nut. The distributors are used from −40 °C to +110 °C, are self-extinguishing and resist oil, acids and petrol-type chemicals.

Where PVC corrugated conduit is enough

In general-purpose electrical installations, where the temperature stays below +70 °C and there is no halogen-free requirement, PVC corrugated conduit is a practical choice. It is made to EN 61386, has 450 N compression and 250 N tensile strength, and comes in 30-metre coils.

Plastic spiral conduit and PE coil pipes

The Plastic Spiral Conduit and the PE & Halogen-Free Coil Pipes used in building installations belong to the same product group. Plastic spiral conduit is made in the 350 N light series, in standard and halogen-free types, from Ø14 to Ø32 mm. The coil pipes come in the 320 N light and 750 N medium series, from Ø14 to Ø63 mm; for a type with a pulling wire inside there is also plastic spiral conduit with guide wire.

Which one to choose?

  • Temperatures above +70 °C: polyamide.
  • Machine wiring and moving equipment: polyamide.
  • A halogen-free requirement: polyamide or halogen-free plastic spiral conduit.
  • General-purpose, fixed installations: PVC corrugated conduit.
  • Fitting over an existing cable bundle without disconnecting it: split polyamide conduit.

Tell us about your application and the temperature; our sales team will suggest the right conduit and connectors with their item codes.

Polyamide conduit sizes

Our polyamide corrugated conduit is made in black and grey in 13 sizes; the table gives each size's inner and outer diameter, its minimum bending radius and its coil length. The split polyamide conduit comes in the same sizes.

NWInner diameter (mm)Outer diameter (mm)Bending radius (mm)Coil (m)
6.56.71015100
8.58.711.715100
101013.220100
1212.615.830100
1414.218.54050
1716.821.44550
1919.5245050
222225.45050
2323.528.75550
2626.131.36025
2928.934.56525
3636.342.58025
4847.654.49025

Does polyamide conduit burn?

Polyamide corrugated conduit is rated UL94 V2 and is self-extinguishing: once the flame source is removed, it does not keep burning. Being halogen-free, it gives off no halogen gases when it burns.

Which connectors does polyamide conduit take?

Polyamide conduit connects with Polyamide Conduit Connectors & Accessories. The straight and compression connectors come with metric and PG threads, the 90° elbow types with PG threads; with a suitable gasket the connectors seal to IP67. Capped clips fix the conduit to a surface, and Y and T distributors split a run in two or three.

What does the NW size mean?

NW (Nennweite) is the nominal width of polyamide conduit and roughly matches its inner diameter: NW 17, for example, is 16.8 mm inside. For connectors and clips, the outer diameter matters too; the table above gives both diameters.

Related products

More articles

  • Guide5 min read

    Flexible steel conduit sizes: inch, ID and OD table

    Flexible steel conduit is made in 18 sizes from 1/4" to 4" and is chosen by its inner diameter: 1/2" conduit, for example, is 16 mm inside and 20 mm outside. The inch value is a name; conduit, fittings and clamps are matched by their millimetre dimensions.

  • Guide4 min read

    Cable glands explained: what they do and how to choose

    A cable gland is the fitting that keeps water and dust out where a cable enters an enclosure or device and anchors the cable against pulling. The right gland is chosen by four things: the cable's outer diameter, the thread type, the thread length and the environment.

  • Guide3 min read

    Cable trunking or rigid PVC conduit? Types and sizes

    Cable trunking is a profile with an opening cover, practical for surface runs and panel wiring where cables will be added later. Rigid PVC conduit carries cables in a closed tube and is made for surface and concealed installations. The choice depends on how much protection the cable needs and whether it will change.

  • Guide3 min read

    What is EMT conduit? How it differs from other conduit

    EMT (electrical metallic tubing) is thin-wall, threadless galvanized steel conduit for electrical installations inside buildings. Its ends are not threaded; it is joined with screw-type or compression couplings and bent to change direction.

  • Guide3 min read

    How to connect flexible conduit to a fitting

    Flexible conduit is connected to a fitting in four steps: choose the fitting, cut the conduit, seat it and tighten the cap, then fix the fitting with its nut. For a sealed run, conduit and fitting must share the same protection class.

  • Guide3 min read

    Galvanized or stainless steel conduit? A comparison

    Galvanized flexible steel conduit works from −50 °C to +300 °C and covers most general installations. Stainless steel conduit works from −100 °C to +600 °C and is made for corrosive environments. The choice comes down to temperature, chemicals and moisture.

  • Guide3 min read

    PVC-coated vs halogen-free (LSZH) conduit

    PVC-coated and halogen-free coated conduits protect the steel core from moisture, oil and dust in the same way; they differ in fire behaviour and temperature. A halogen-free (LSZH) coating gives off little smoke and no halogen gases in a fire, so it is chosen for crowded indoor spaces.

  • Guide3 min read

    Liquid-tight conduit: where and why it is used

    Liquid-tight conduit is galvanized flexible steel conduit enclosed in a thick PVC or halogen-free jacket, rated IP66–IP69. It is used wherever cables meet water, dust, petrol or solvents.

  • Guide4 min read

    How to choose a flexible steel conduit

    Four questions decide the right flexible steel conduit: ambient temperature, exposure to water and dust, electromagnetic interference, and cable size. Temperature picks the material, sealing picks the coating, interference picks the braid, and the cable bundle picks the diameter.

  • Technical3 min read

    What does IP68 mean? IP ratings explained

    In an IP code the first digit is protection against dust and solid objects, the second against water. IP68 means fully dust-tight and able to withstand continuous immersion.