PVC-coated vs halogen-free (LSZH) conduit

Fleks Elektrik Technical Team

In short

PVC-coated and halogen-free coated conduits protect the steel core from moisture, oil and dust in the same way; they differ in fire behaviour and temperature. A halogen-free (LSZH) coating gives off little smoke and no halogen gases in a fire, so it is chosen for crowded indoor spaces.

What is coated flexible conduit?

A coated steel conduit is galvanized flexible steel conduit with a plastic coating. The steel body protects the cable from crushing and cuts, and the coating adds protection against moisture, oil and dust. The coating can be PVC or halogen-free (LSZH). Both come in the same sizes: 18 sizes from 1/4" to 4".

Comparison

FeaturePVC-coatedHalogen-free (LSZH) coated
CoatingPVCHalogen-free, low smoke
Protection classIP54–IP65IP54–IP66
Operating temperature−25 °C / +90 °C−40 °C / +100 °C
Fire behaviourLow flame and smokeLow smoke, zero halogen; self-extinguishing
Chemical resistanceResists moisture and oilResists petrol, solvents and acids
ColoursBlack, white, greyBlack, white, grey
Sizes1/4"–4", 18 sizes1/4"–4", 18 sizes

Why halogens matter

PVC contains chlorine. When PVC burns it gives off dense, dark smoke and corrosive gases such as hydrogen chloride: the smoke cuts visibility on escape routes, and the gas is harmful to breathe and corrodes electronic equipment. A halogen-free coating gives off little smoke and no halogen gases in a fire; our halogen-free coated conduit also contains no halogens, sulphur or phosphorus.

When to choose halogen-free

In indoor spaces where many people gather and escape takes time, a halogen-free coating is preferred: hospitals, schools, tunnels and shopping centres, for example. If the project specification asks for halogen-free material, make sure that not only the conduit but also the fittings, boxes and cable are halogen-free; our halogen-free flush-mounting boxes, polyamide conduit connectors and polyamide cable glands can be used for this.

When PVC-coated is enough

Where there is moisture, oil and dust but no crowd, PVC-coated conduit is enough: machine installations in factories, warehouses and plant rooms, for example. It also suits electrical installations in narrow spaces, in places with insufficient ventilation and where high safety is needed. The guide-wire type, which makes pulling cable easier on long runs, comes only in the PVC-coated series.

Cold and temperature

Halogen-free coated conduit can be used in the cold down to −40 °C, PVC-coated conduit down to −25 °C. The upper limit is also a little higher for halogen-free: +100 °C against +90 °C. In very cold environments and near hot machine parts, that difference matters. The black halogen-free type is also UV resistant.

More water and dust: the liquid-tight types

Coated conduits protect against splashing water and water jets. Where there is direct contact with water, petrol or solvents, a liquid-tight type is needed, and it too comes with two jackets. The PVC-jacketed conduit is rated IP66–IP68 and works from −20 °C to +105 °C; the halogen-free jacketed conduit is rated IP66–IP69 and works from −40 °C to +100 °C. Both connect with the Liquid-Tight Conduit Fitting or the Compression (Silok) Conduit Gland.

Summary

  • Crowded indoor space or a halogen-free requirement: halogen-free (LSZH) coated conduit.
  • Moisture, oil and dust, no crowd: PVC-coated conduit.
  • Cold below −25 °C: halogen-free coated conduit.
  • Long run, easy cable pulling: PVC-coated conduit with guide wire.
  • Direct contact with water and solvents: liquid-tight conduit (PVC or halogen-free jacketed).

Send us your project specification or the conditions on site; our sales team will suggest the right conduit and fitting with their item codes.

What does LSZH stand for?

LSZH stands for low smoke zero halogen. It describes materials that give off little smoke in a fire and contain no halogens such as chlorine or bromine.

Which colours do the coated conduits come in?

Our PVC-coated and halogen-free coated conduits come in black, white and grey. The black halogen-free coated type is UV resistant, so black is the colour to choose where there is sun.

Is there halogen-free conduit with a guide wire?

The guide-wire type is made only in the PVC-coated series, with the same data as the PVC-coated conduit: IP54–IP65 protection, working from −25 °C to +90 °C, 18 sizes from 1/4" to 4". On a halogen-free run that needs a long pull, choosing the next size up makes pulling the cable easier.

Related products

More articles

  • Guide5 min read

    Flexible steel conduit sizes: inch, ID and OD table

    Flexible steel conduit is made in 18 sizes from 1/4" to 4" and is chosen by its inner diameter: 1/2" conduit, for example, is 16 mm inside and 20 mm outside. The inch value is a name; conduit, fittings and clamps are matched by their millimetre dimensions.

  • Guide4 min read

    Cable glands explained: what they do and how to choose

    A cable gland is the fitting that keeps water and dust out where a cable enters an enclosure or device and anchors the cable against pulling. The right gland is chosen by four things: the cable's outer diameter, the thread type, the thread length and the environment.

  • Guide4 min read

    Polyamide vs PVC corrugated conduit: the difference

    Polyamide corrugated conduit works from −40 °C to +120 °C, is halogen-free and self-extinguishing. PVC corrugated conduit works from −20 °C to +70 °C and is made for general-purpose installations. Polyamide is chosen where it is hot, where things move, or where halogen-free material is required.

  • Guide3 min read

    Cable trunking or rigid PVC conduit? Types and sizes

    Cable trunking is a profile with an opening cover, practical for surface runs and panel wiring where cables will be added later. Rigid PVC conduit carries cables in a closed tube and is made for surface and concealed installations. The choice depends on how much protection the cable needs and whether it will change.

  • Guide3 min read

    What is EMT conduit? How it differs from other conduit

    EMT (electrical metallic tubing) is thin-wall, threadless galvanized steel conduit for electrical installations inside buildings. Its ends are not threaded; it is joined with screw-type or compression couplings and bent to change direction.

  • Guide3 min read

    How to connect flexible conduit to a fitting

    Flexible conduit is connected to a fitting in four steps: choose the fitting, cut the conduit, seat it and tighten the cap, then fix the fitting with its nut. For a sealed run, conduit and fitting must share the same protection class.

  • Guide3 min read

    Galvanized or stainless steel conduit? A comparison

    Galvanized flexible steel conduit works from −50 °C to +300 °C and covers most general installations. Stainless steel conduit works from −100 °C to +600 °C and is made for corrosive environments. The choice comes down to temperature, chemicals and moisture.

  • Guide3 min read

    Liquid-tight conduit: where and why it is used

    Liquid-tight conduit is galvanized flexible steel conduit enclosed in a thick PVC or halogen-free jacket, rated IP66–IP69. It is used wherever cables meet water, dust, petrol or solvents.

  • Guide4 min read

    How to choose a flexible steel conduit

    Four questions decide the right flexible steel conduit: ambient temperature, exposure to water and dust, electromagnetic interference, and cable size. Temperature picks the material, sealing picks the coating, interference picks the braid, and the cable bundle picks the diameter.

  • Technical3 min read

    What does IP68 mean? IP ratings explained

    In an IP code the first digit is protection against dust and solid objects, the second against water. IP68 means fully dust-tight and able to withstand continuous immersion.