Galvanized or stainless steel conduit? A comparison

Fleks Elektrik Technical Team

In short

Galvanized flexible steel conduit works from −50 °C to +300 °C and covers most general installations. Stainless steel conduit works from −100 °C to +600 °C and is made for corrosive environments. The choice comes down to temperature, chemicals and moisture.

The short answer

In dry or normal indoor conditions and up to +300 °C, galvanized flexible steel conduit is enough. Where there are chemicals, sea air, constant wetness, or temperatures above +300 °C (up to +600 °C) or below −50 °C (down to −100 °C), choose stainless steel conduit.

Comparison table

FeatureGalvanized steel conduitStainless steel conduit
MaterialGalvanized steel stripAISI 304 or AISI 316L stainless steel
Operating temperature−50 °C / +300 °C−100 °C / +600 °C
Protection classIP40IP40
Key featuresLight square-lock profile, small bending radius, smooth boreResists petrol, solvents and acids; free of halogens, sulphur and phosphorus; non-combustible; UV resistant
Sizes1/4"–4", 18 sizes1/4"–4", 18 sizes, in two grades
Coils50, 25 and 15 m50, 25 and 10 m
FittingSteel conduit fittingSteel conduit fitting

How galvanizing protects

On galvanized steel the zinc layer separates the steel from moisture and oxygen; even at a scratch the zinc corrodes first and goes on protecting the steel. In dry and normal indoor conditions this protection is enough for most applications. Acids, salt and constant wetness use the zinc up quickly, and those environments need stainless or coated conduit.

Stainless steel: 304 or 316L?

Stainless steel owes its corrosion resistance to a thin chromium oxide layer that forms on its surface by itself. AISI 304 is enough for general corrosive environments. AISI 316L, thanks to the molybdenum in its alloy, resists chlorides, sea air and salt water better; the L stands for low carbon.

Our stainless steel conduit is made in both grades in the same sizes; the only difference is the outer diameter of the 3/8" size, 17 mm in 304 and 18 mm in 316L. The item code tells the grade: 1/2" conduit, for example, is F.03.1016 in grade 304 and F.03.2016 in grade 316L.

Why the temperature limit matters

As temperatures rise, the zinc coating and the steel lose their properties; our galvanized conduit is used up to +300 °C. Stainless steel conduit works up to +600 °C and withstands cold down to −100 °C. At very hot points such as furnaces, heat treatment lines and exhausts, or in very cold environments, that difference is decisive.

Braided types come both ways too

For runs that need shielding against electromagnetic interference we make galvanized conduit with either a galvanized steel braid or a stainless steel braid. Both work from −100 °C to +300 °C, are non-combustible and are made in 8 sizes from 1/4" to 2"; the stainless braid gives the outer surface better resistance to corrosion.

Which for which environment?

EnvironmentRecommendation
Dry indoor areas, panel and machine installationsGalvanized
Damp, oily or dusty but chemical-freePVC-coated galvanized (IP54–IP65)
Chemicals, acids or solventsStainless (304 or 316L)
Sea air, chlorides and saltStainless 316L
Above +300 °C (up to +600 °C)Stainless
Direct contact with water and dustLiquid-tight jacketed conduit

There is no difference in fittings: both conduits connect with the Steel Conduit Fitting. Tell us about your environment and temperature, and we will suggest the right conduit and fitting with their item codes.

Does stainless conduit never rust?

Stainless steel resists corrosion very well thanks to the chromium oxide layer on its surface, but it is not guaranteed to stay spotless in every condition: in chloride and salt environments grade 304 can stain. There, the molybdenum-bearing grade 316L is preferred.

Can galvanized conduit be used outdoors?

Uncoated galvanized conduit is rated IP40 and does not keep water out; where rain and moisture reach it, the cable is not protected and the zinc is used up faster. Outdoors, choose PVC-coated conduit (IP54–IP65) or liquid-tight jacketed conduit (IP66–IP69).

Stainless-braided or stainless steel conduit?

Stainless steel conduit is made entirely of stainless steel and works up to +600 °C. Stainless-braided conduit is galvanized conduit with a stainless steel braid over it; it gives very high shielding against electromagnetic interference and works from −100 °C to +300 °C. Choose stainless conduit for high temperatures and corrosion, the braided type for shielding.

Related products

More articles

  • Guide5 min read

    Flexible steel conduit sizes: inch, ID and OD table

    Flexible steel conduit is made in 18 sizes from 1/4" to 4" and is chosen by its inner diameter: 1/2" conduit, for example, is 16 mm inside and 20 mm outside. The inch value is a name; conduit, fittings and clamps are matched by their millimetre dimensions.

  • Guide4 min read

    Cable glands explained: what they do and how to choose

    A cable gland is the fitting that keeps water and dust out where a cable enters an enclosure or device and anchors the cable against pulling. The right gland is chosen by four things: the cable's outer diameter, the thread type, the thread length and the environment.

  • Guide4 min read

    Polyamide vs PVC corrugated conduit: the difference

    Polyamide corrugated conduit works from −40 °C to +120 °C, is halogen-free and self-extinguishing. PVC corrugated conduit works from −20 °C to +70 °C and is made for general-purpose installations. Polyamide is chosen where it is hot, where things move, or where halogen-free material is required.

  • Guide3 min read

    Cable trunking or rigid PVC conduit? Types and sizes

    Cable trunking is a profile with an opening cover, practical for surface runs and panel wiring where cables will be added later. Rigid PVC conduit carries cables in a closed tube and is made for surface and concealed installations. The choice depends on how much protection the cable needs and whether it will change.

  • Guide3 min read

    What is EMT conduit? How it differs from other conduit

    EMT (electrical metallic tubing) is thin-wall, threadless galvanized steel conduit for electrical installations inside buildings. Its ends are not threaded; it is joined with screw-type or compression couplings and bent to change direction.

  • Guide3 min read

    How to connect flexible conduit to a fitting

    Flexible conduit is connected to a fitting in four steps: choose the fitting, cut the conduit, seat it and tighten the cap, then fix the fitting with its nut. For a sealed run, conduit and fitting must share the same protection class.

  • Guide3 min read

    PVC-coated vs halogen-free (LSZH) conduit

    PVC-coated and halogen-free coated conduits protect the steel core from moisture, oil and dust in the same way; they differ in fire behaviour and temperature. A halogen-free (LSZH) coating gives off little smoke and no halogen gases in a fire, so it is chosen for crowded indoor spaces.

  • Guide3 min read

    Liquid-tight conduit: where and why it is used

    Liquid-tight conduit is galvanized flexible steel conduit enclosed in a thick PVC or halogen-free jacket, rated IP66–IP69. It is used wherever cables meet water, dust, petrol or solvents.

  • Guide4 min read

    How to choose a flexible steel conduit

    Four questions decide the right flexible steel conduit: ambient temperature, exposure to water and dust, electromagnetic interference, and cable size. Temperature picks the material, sealing picks the coating, interference picks the braid, and the cable bundle picks the diameter.

  • Technical3 min read

    What does IP68 mean? IP ratings explained

    In an IP code the first digit is protection against dust and solid objects, the second against water. IP68 means fully dust-tight and able to withstand continuous immersion.