Flexible steel conduit sizes: inch, ID and OD table

Fleks Elektrik Technical Team

In short

Flexible steel conduit is made in 18 sizes from 1/4" to 4" and is chosen by its inner diameter: 1/2" conduit, for example, is 16 mm inside and 20 mm outside. The inch value is a name; conduit, fittings and clamps are matched by their millimetre dimensions.

How to read a size

Every flexible steel conduit row in our catalogue gives the item code, the nominal size, the trade size (inches), the inner diameter, the outer diameter and the coil length. The nominal size is the conduit's name in millimetres and usually equals the inner diameter: conduit number 16 is 16 mm inside. The trade size is a name given in inches, like 1/2" or 3/4", and is not the conduit's actual diameter.

So when choosing conduit, look at the millimetre dimensions, not the inch value. The inner diameter sets the space for the cable or bundle; the outer diameter sets what fittings, clamps and straps have to grip.

Galvanized flexible steel conduit sizes

Our galvanized flexible steel conduit is made in 18 sizes. The in-between sizes (14, 18, 29, 32, 37, 42 and 45) have no inch equivalent and go by their millimetre size.

CodeNominal sizeTrade sizeInner diameter (mm)Outer diameter (mm)Coil (m)
F.01.100991/4"912.550
F.01.1011113/8"111550
F.01.101414–141850
F.01.1016161/2"162050
F.01.101818–182250
F.01.1021213/4"212550
F.01.1026261"263025
F.01.102929–293425
F.01.103232–323725
F.01.1035351 1/4"354025
F.01.103737–374125
F.01.1040401 1/2"404525
F.01.104242–424725
F.01.104545–455125
F.01.1050502"505525
F.01.1063632 1/2"636715
F.01.1075753"758115
F.01.11001004"10211015

Steel conduit with guide wire and the PVC-coated and halogen-free coated steel conduits are made in the same 18 sizes; in our catalogue their inner and outer diameters and coil lengths match this table.

Stainless steel conduit sizes differ slightly

Our stainless steel conduit is made in two grades, AISI 304 and AISI 316L, again in 18 sizes, but some diameters differ from the galvanized series. In the stainless series, for example, 1/4" conduit is 11 mm inside and 1/2" conduit 15.5 mm inside. Stainless sizes of 2 1/2" and above also come in 10-metre coils.

Trade sizeGalvanized inner / outer (mm)Stainless 304 inner / outer (mm)
1/4"9 / 12.511 / 15
3/8"11 / 1514 / 17
1/2"16 / 2015.5 / 19,5
3/4"21 / 2520.5 / 24,5
1"26 / 3025.5 / 31
1 1/4"35 / 4034.5 / 40
1 1/2"40 / 4539.5 / 45,5
2"50 / 5550 / 55
2 1/2"63 / 6763 / 67
3"75 / 8175 / 81
4"102 / 110102 / 110

Grade 316L has the same dimensions as 304; the only difference is the outer diameter of the 3/8" size, 18 mm instead of 17.

Size ranges of braided and liquid-tight conduit

A braid or a thick jacket makes the outer diameter larger. At 1/2", for example, the outer diameter is 20 mm on galvanized conduit, 21 mm on steel-braided galvanized conduit, 21.1 mm on liquid-tight PVC-jacketed conduit and 23.4 mm on liquid-tight steel-braided conduit. Fittings, clamps and straps are chosen by this outer diameter.

Conduit typeSize rangeNumber of sizesCoil (m)
Galvanized, guide wire, PVC and halogen-free coated1/4"–4"1850, 25, 15
Stainless (304, 316L)1/4"–4"1850, 25, 10
Steel-braided (galvanized, stainless, PVC-jacketed)1/4"–2"830, 15
Liquid-tight steel-braided1/4"–2"830, 15
Liquid-tight (PVC and halogen-free jacketed)1/4"–4"1130, 15, 7.5

Four steps to the right size

  • Measure the cable's outer diameter, or the widest point of the bundle; the conduit's inner diameter should be comfortably larger.
  • If the run is long with many bends, consider the next size up or a guide-wire type; the cable pulls more easily.
  • Choose the fitting by the conduit size; the fitting tables give the conduit size in a column of their own. If in doubt, just give our sales team the conduit's item code.
  • Order by item code: the code alone defines the size and the material.

Coil lengths and ordering

Coil lengths are fixed by size: in the galvanized series 1/4" to 3/4" (in-between sizes included) come in 50 m, 1" to 2" in 25 m and larger sizes in 15 m; in stainless the large sizes come in 10 m. Divide the total length of your runs by the coil length to see how many coils you need.

Easily confused

The same inch name stands for different diameters in different product families: 1/2" flexible steel conduit is 20 mm outside, 1/2" EMT 17.93 mm. Polyamide corrugated conduit goes by NW size, not inches (NW 17, for example, is 16.8 mm inside and 21.4 mm outside). So always check the product's own table.

How many mm is 1/2 inch flexible steel conduit?

In galvanized flexible steel conduit, the 1/2" size is 16 mm inside and 20 mm outside; its nominal size is 16 and it comes in 50-metre coils. In the stainless series, 1/2" conduit is 15.5 mm inside and 19.5 mm outside.

How many mm are 3/4 inch and 1 inch conduit?

In the galvanized series, 3/4" conduit is 21 mm inside and 25 mm outside, and 1" conduit 26 mm inside and 30 mm outside. The 3/4" size comes in 50-metre coils and the 1" size in 25-metre coils.

How many mm is 2 inch conduit?

In the galvanized and stainless series, 2" conduit is 50 mm inside and 55 mm outside. On steel-braided galvanized conduit the 2" size is 52 mm inside and 59 mm outside; on liquid-tight PVC-jacketed conduit, 51.5 mm inside and 59.8 mm outside.

Which sizes have no inch name?

The in-between sizes 14, 18, 29, 32, 37, 42 and 45 in the galvanized series have no inch equivalent and are ordered by their nominal size in millimetres. Size 18, for example, is 18 mm inside and 22 mm outside. These sizes give a better-fitting space for a cable bundle that falls between two inch sizes.

Related products

More articles

  • Guide4 min read

    Cable glands explained: what they do and how to choose

    A cable gland is the fitting that keeps water and dust out where a cable enters an enclosure or device and anchors the cable against pulling. The right gland is chosen by four things: the cable's outer diameter, the thread type, the thread length and the environment.

  • Guide4 min read

    Polyamide vs PVC corrugated conduit: the difference

    Polyamide corrugated conduit works from −40 °C to +120 °C, is halogen-free and self-extinguishing. PVC corrugated conduit works from −20 °C to +70 °C and is made for general-purpose installations. Polyamide is chosen where it is hot, where things move, or where halogen-free material is required.

  • Guide3 min read

    Cable trunking or rigid PVC conduit? Types and sizes

    Cable trunking is a profile with an opening cover, practical for surface runs and panel wiring where cables will be added later. Rigid PVC conduit carries cables in a closed tube and is made for surface and concealed installations. The choice depends on how much protection the cable needs and whether it will change.

  • Guide3 min read

    What is EMT conduit? How it differs from other conduit

    EMT (electrical metallic tubing) is thin-wall, threadless galvanized steel conduit for electrical installations inside buildings. Its ends are not threaded; it is joined with screw-type or compression couplings and bent to change direction.

  • Guide3 min read

    How to connect flexible conduit to a fitting

    Flexible conduit is connected to a fitting in four steps: choose the fitting, cut the conduit, seat it and tighten the cap, then fix the fitting with its nut. For a sealed run, conduit and fitting must share the same protection class.

  • Guide3 min read

    Galvanized or stainless steel conduit? A comparison

    Galvanized flexible steel conduit works from −50 °C to +300 °C and covers most general installations. Stainless steel conduit works from −100 °C to +600 °C and is made for corrosive environments. The choice comes down to temperature, chemicals and moisture.

  • Guide3 min read

    PVC-coated vs halogen-free (LSZH) conduit

    PVC-coated and halogen-free coated conduits protect the steel core from moisture, oil and dust in the same way; they differ in fire behaviour and temperature. A halogen-free (LSZH) coating gives off little smoke and no halogen gases in a fire, so it is chosen for crowded indoor spaces.

  • Guide3 min read

    Liquid-tight conduit: where and why it is used

    Liquid-tight conduit is galvanized flexible steel conduit enclosed in a thick PVC or halogen-free jacket, rated IP66–IP69. It is used wherever cables meet water, dust, petrol or solvents.

  • Guide4 min read

    How to choose a flexible steel conduit

    Four questions decide the right flexible steel conduit: ambient temperature, exposure to water and dust, electromagnetic interference, and cable size. Temperature picks the material, sealing picks the coating, interference picks the braid, and the cable bundle picks the diameter.

  • Technical3 min read

    What does IP68 mean? IP ratings explained

    In an IP code the first digit is protection against dust and solid objects, the second against water. IP68 means fully dust-tight and able to withstand continuous immersion.