Guide · 3 min read
How to connect flexible conduit to a fitting
Fleks Elektrik Technical Team
In short
Flexible conduit is connected to a fitting in four steps: choose the fitting, cut the conduit, seat it and tighten the cap, then fix the fitting with its nut. For a sealed run, conduit and fitting must share the same protection class.
Before you start: the right fitting
Each type of conduit has its own fitting. Galvanized, stainless and guide-wire steel conduits connect with the Steel Conduit Fitting. Liquid-tight PVC and halogen-free jacketed conduits and the liquid-tight steel-braided conduit connect with the Liquid-Tight Conduit Fitting or the Compression (Silok) Conduit Gland. Decide at the outset between a fixed and a swivel type, and on the thread: NPT, metric or PG.
| Conduit | Fitting | Fitting protection class |
|---|---|---|
| Galvanized, stainless and guide-wire steel | Steel conduit fitting (indoor) | IP54 |
| Liquid-tight PVC and halogen-free jacketed | Liquid-tight conduit fitting (outdoor) or compression (Silok) gland | IP67 |
| Liquid-tight steel-braided | Liquid-tight conduit fitting or compression (Silok) gland | IP67 |
| Going from an EMT run to flexible conduit | EMT to flexible conduit connectors | — |
Fixed or swivel?
On a fixed type the body and thread turn as one piece, so the conduit wants to turn as the fitting is screwed into the enclosure. On a swivel type the thread turns independently of the body; if the conduit is already fitted, or must not be twisted, a swivel type makes installation easier. Both come in the same sizes and threads.
Step 1: Cut the conduit
Cut the conduit to length, square to its axis; flexible steel conduit can be cut with a hacksaw or a suitable conduit cutter. Then remove the burr from the end: a sharp edge damages both the fitting's seal and the sheath of the cable that will run through it. On coated and jacketed conduit, make sure the coating stays clean and untorn at the cut.
Step 2: Fit the fitting to the conduit
Slide the cap nut, and the seal and ring if there are any, over the conduit. Fit the ferrule into the conduit end; on most fittings the ferrule is turned into the spiral, where it supports the end from inside and keeps the cable off the edge. Push the conduit home against the fitting body and tighten the cap nut by hand, then with a spanner.
On liquid-tight fittings, tightening the cap presses the seal onto the conduit jacket, and that is where the seal is made. On the compression (Silok) gland, the insert seal grips the jacket and acts as a gasket once the gland is fitted to the conduit and tightened.
Step 3: Connect the fitting to the enclosure
Check that the hole in the enclosure matches the fitting's thread: a metric fitting goes into a metric hole, a PG fitting into a PG hole, and an NPT fitting screws into a threaded entry. Pass the fitting through the hole and tighten it from the inside with its nut; if the hole is threaded, screw the fitting straight in. Make sure the O-ring sits properly between the body and the enclosure.
Step 4: Check
- The conduit must not come out of the fitting or turn when pulled by hand.
- The seal and O-ring must not be crushed or out of place.
- The conduit must not bend sharply right behind the fitting; start the bend a little way from it.
- The cable must pass through the conduit and fitting without being forced.
Joining conduit to conduit, or to EMT
To join two flexible conduits end to end, use a flexible-to-flexible coupling; to go from a rigid EMT run to flexible conduit, use EMT to Flexible Conduit Connectors. The group also includes screw-type EMT-to-flexible connectors, screw-type and 90° steel conduit connectors, liquid-tight connectors with gas threads and metal ferrules, from 1/2" to 2".
Common mistakes
- Using the IP54 steel conduit fitting on liquid-tight conduit: the run drops to the fitting's class.
- Not deburring: the seal and the cable sheath are damaged.
- Overtightening the cap: the seal is crushed and seals less well.
- Forcing a fitting into a hole whose thread does not match.
- Using the indoor type outdoors: there is an outdoor liquid-tight fitting for that.
If you are not sure of the fitting or conduit size, send our sales team the conduit's item code; we will suggest the right fitting with its item code.
What tools are needed?
A hacksaw or conduit cutter to cut the conduit, a file or deburring tool for the burr, and a spanner of the right size for the cap nut and lock nut are enough. On coated and jacketed conduit, a sharp utility knife helps to cut the coating cleanly.
How do I find the fitting size?
In the fitting tables, each row gives the thread (its NPT, metric and PG versions) and the conduit size in separate columns. Decide the conduit size first, then the thread that matches the hole in the enclosure. The steel conduit fitting with a 1/2" NPT thread, for example, has M20×1.5 as its metric and Pg 16 as its PG version. If in doubt, send us the conduit's code.
Can the fitting be used outdoors?
The steel conduit fitting is an indoor type. Outdoors and where water splashes, use the Liquid-Tight Conduit Fitting, designed as an outdoor type, together with liquid-tight conduit; it works from −45 °C to +105 °C and is rated IP67.
Related products

- IP40

- IP54

- IP67

- IP67

More articles

Guide5 min read
Flexible steel conduit sizes: inch, ID and OD table
Flexible steel conduit is made in 18 sizes from 1/4" to 4" and is chosen by its inner diameter: 1/2" conduit, for example, is 16 mm inside and 20 mm outside. The inch value is a name; conduit, fittings and clamps are matched by their millimetre dimensions.

Guide4 min read
Cable glands explained: what they do and how to choose
A cable gland is the fitting that keeps water and dust out where a cable enters an enclosure or device and anchors the cable against pulling. The right gland is chosen by four things: the cable's outer diameter, the thread type, the thread length and the environment.

Guide4 min read
Polyamide vs PVC corrugated conduit: the difference
Polyamide corrugated conduit works from −40 °C to +120 °C, is halogen-free and self-extinguishing. PVC corrugated conduit works from −20 °C to +70 °C and is made for general-purpose installations. Polyamide is chosen where it is hot, where things move, or where halogen-free material is required.

Guide3 min read
Cable trunking or rigid PVC conduit? Types and sizes
Cable trunking is a profile with an opening cover, practical for surface runs and panel wiring where cables will be added later. Rigid PVC conduit carries cables in a closed tube and is made for surface and concealed installations. The choice depends on how much protection the cable needs and whether it will change.

Guide3 min read
What is EMT conduit? How it differs from other conduit
EMT (electrical metallic tubing) is thin-wall, threadless galvanized steel conduit for electrical installations inside buildings. Its ends are not threaded; it is joined with screw-type or compression couplings and bent to change direction.

Guide3 min read
Galvanized or stainless steel conduit? A comparison
Galvanized flexible steel conduit works from −50 °C to +300 °C and covers most general installations. Stainless steel conduit works from −100 °C to +600 °C and is made for corrosive environments. The choice comes down to temperature, chemicals and moisture.

Guide3 min read
PVC-coated vs halogen-free (LSZH) conduit
PVC-coated and halogen-free coated conduits protect the steel core from moisture, oil and dust in the same way; they differ in fire behaviour and temperature. A halogen-free (LSZH) coating gives off little smoke and no halogen gases in a fire, so it is chosen for crowded indoor spaces.

Guide3 min read
Liquid-tight conduit: where and why it is used
Liquid-tight conduit is galvanized flexible steel conduit enclosed in a thick PVC or halogen-free jacket, rated IP66–IP69. It is used wherever cables meet water, dust, petrol or solvents.

Guide4 min read
How to choose a flexible steel conduit
Four questions decide the right flexible steel conduit: ambient temperature, exposure to water and dust, electromagnetic interference, and cable size. Temperature picks the material, sealing picks the coating, interference picks the braid, and the cable bundle picks the diameter.

Technical3 min read
What does IP68 mean? IP ratings explained
In an IP code the first digit is protection against dust and solid objects, the second against water. IP68 means fully dust-tight and able to withstand continuous immersion.

Technical3 min read
PG vs metric gland threads: the difference and which to choose
PG and metric are two separate thread standards for cable glands, and they do not fit each other. New designs use metric threads; for existing enclosures with PG entries, choose a PG gland or an adapter.