Guide · 4 min read
How to choose a flexible steel conduit
Fleks Elektrik Technical Team
In short
Four questions decide the right flexible steel conduit: ambient temperature, exposure to water and dust, electromagnetic interference, and cable size. Temperature picks the material, sealing picks the coating, interference picks the braid, and the cable bundle picks the diameter.
1. How hot is the environment?
Material selection starts with operating temperature. For uncoated flexible steel conduit the grade of steel sets the limit: galvanized steel works from −50 °C to +300 °C and stainless steel from −100 °C to +600 °C. Galvanized is enough for most machine, panel and building installations; stainless is chosen for very hot or very cold spots and for corrosive environments.
| Material | Operating temperature | When to choose it |
|---|---|---|
| Galvanized steel | −50 °C / +300 °C | Most machine, panel and building installations |
| Stainless steel 304 / 316L | −100 °C / +600 °C | Corrosive environments, very high or very low temperatures |
On coated conduits the coating, not the steel, sets the limit: PVC-coated conduit works from −25 °C to +90 °C, halogen-free coated conduit from −40 °C to +100 °C and liquid-tight PVC-jacketed conduit from −20 °C to +105 °C.
2. Is there water, oil or dust?
Uncoated flexible steel conduit is rated IP40: it protects cables from crushing and cuts but does not keep water out. Wet, oily or dusty places need a coated type. PVC-coated conduit gives IP54–IP65 protection against moisture, oil and dust. Where water, petrol or solvents come into direct contact, choose the thick-jacketed liquid-tight conduit: the PVC-jacketed type gives IP66–IP68 and the halogen-free jacketed type up to IP69.
| Conduit type | Protection class | Typical environment |
|---|---|---|
| Uncoated flexible steel | IP40 | Dry indoor areas, inside machines |
| PVC-coated flexible steel | IP54–IP65 | Moisture, oil and dust |
| Halogen-free coated flexible steel | IP54–IP66 | Crowded indoor spaces |
| Liquid-tight flexible steel | IP66–IP69 | Contact with water, petrol and solvents |
3. Is it an enclosed, crowded space?
In crowded indoor spaces such as hospitals, schools, tunnels and shopping centres, a halogen-free (LSZH) coating is preferred: it gives off little smoke in a fire and releases no halogen gases. Both the coated and the liquid-tight series come in halogen-free versions, and both are self-extinguishing. The halogen-free coated conduit can also be used in the cold down to −40 °C.
4. Is there a risk of electromagnetic interference?
Where drive, motor and signal cables run side by side, choose a steel-braided type; the braid gives very high shielding against electromagnetic interference (EMI). The braided series comes with a galvanized braid, a stainless braid, a PVC jacket or a liquid-tight jacket. If sealing is needed as well, the liquid-tight braided type combines both at IP66.
5. Which diameter?
Choose the conduit by its inner diameter: take the size the cable bundle passes through easily. The inch value is a name, not an actual diameter, so look at the inner diameter in millimetres in the table. For fittings and clamps the outer diameter is what counts. On long runs with many bends, a guide-wire type makes cable pulling easier.
| Trade size | Inner diameter | Outer diameter |
|---|---|---|
| 1/4" | 9 mm | 12.5 mm |
| 3/8" | 11 mm | 15 mm |
| 1/2" | 16 mm | 20 mm |
| 3/4" | 21 mm | 25 mm |
| 1" | 26 mm | 30 mm |
| 1 1/4" | 35 mm | 40 mm |
| 1 1/2" | 40 mm | 45 mm |
| 2" | 50 mm | 55 mm |
| 2 1/2" | 63 mm | 67 mm |
| 3" | 75 mm | 81 mm |
| 4" | 102 mm | 110 mm |
The table shows the inch sizes of galvanized flexible steel conduit; for the in-between sizes and coil lengths see our article “Flexible steel conduit sizes”.
6. Is there movement or vibration?
Thanks to their light square-lock profile, our steel conduits bend to a very small radius, which helps with the final connection to a machine and on runs that change direction often. On equipment that moves all the time, light and highly flexible polyamide corrugated conduit should also be considered: it works from −40 °C to +120 °C and is rated IP66–IP68.
Don't forget the fitting
A conduit keeps its protection class only with a suitable fitting; a run is only as well protected as its weakest link. Use the IP54 Steel Conduit Fitting for uncoated steel conduit, and the IP67 Liquid-Tight Conduit Fitting or the Compression (Silok) Conduit Gland for liquid-tight conduit. The fittings come with NPT, metric and PG threads; choose the thread that matches the hole in your enclosure.
The choice in short
- Temperature decides the material: galvanized or stainless.
- Water, oil and dust decide the coating: uncoated, PVC-coated or liquid-tight.
- A crowded indoor space calls for a halogen-free coating.
- Where there is a risk of interference, choose a steel-braided type.
- Choose the diameter by the inner diameter to suit the cable bundle; on long runs a guide-wire type helps.
- The fitting must keep the conduit's protection class.
If you are unsure about a run, write to us with the environment, the temperature and the diameter of the cable bundle; our sales team will suggest the right conduit and fitting with their item codes.
Can flexible steel conduit be used outdoors?
Uncoated flexible steel conduit is IP40 and does not keep water out; outdoors, a coated or liquid-tight type is chosen. Where there is sun, the black halogen-free coated and liquid-tight conduits are UV resistant.
When is a guide wire needed?
If the run is long, has many bends, or the conduit is laid before the cable, a guide-wire type makes the job easier: the cable is tied to the wire inside the conduit and pulled through. Our galvanized steel and PVC-coated steel conduits come in guide-wire types from 1/4" to 4", in the same sizes.
Does stainless conduit need a different fitting?
No. Galvanized, stainless and guide-wire steel conduits all connect with the same Steel Conduit Fitting; its body is nickel-plated brass and it is rated IP54.
Related products

- IP40

- IP40

- IP54–IP65

- IP66–IP68

- IP66
- EMI

- IP54
More articles

Guide5 min read
Flexible steel conduit sizes: inch, ID and OD table
Flexible steel conduit is made in 18 sizes from 1/4" to 4" and is chosen by its inner diameter: 1/2" conduit, for example, is 16 mm inside and 20 mm outside. The inch value is a name; conduit, fittings and clamps are matched by their millimetre dimensions.

Guide4 min read
Cable glands explained: what they do and how to choose
A cable gland is the fitting that keeps water and dust out where a cable enters an enclosure or device and anchors the cable against pulling. The right gland is chosen by four things: the cable's outer diameter, the thread type, the thread length and the environment.

Guide4 min read
Polyamide vs PVC corrugated conduit: the difference
Polyamide corrugated conduit works from −40 °C to +120 °C, is halogen-free and self-extinguishing. PVC corrugated conduit works from −20 °C to +70 °C and is made for general-purpose installations. Polyamide is chosen where it is hot, where things move, or where halogen-free material is required.

Guide3 min read
Cable trunking or rigid PVC conduit? Types and sizes
Cable trunking is a profile with an opening cover, practical for surface runs and panel wiring where cables will be added later. Rigid PVC conduit carries cables in a closed tube and is made for surface and concealed installations. The choice depends on how much protection the cable needs and whether it will change.

Guide3 min read
What is EMT conduit? How it differs from other conduit
EMT (electrical metallic tubing) is thin-wall, threadless galvanized steel conduit for electrical installations inside buildings. Its ends are not threaded; it is joined with screw-type or compression couplings and bent to change direction.

Guide3 min read
How to connect flexible conduit to a fitting
Flexible conduit is connected to a fitting in four steps: choose the fitting, cut the conduit, seat it and tighten the cap, then fix the fitting with its nut. For a sealed run, conduit and fitting must share the same protection class.

Guide3 min read
Galvanized or stainless steel conduit? A comparison
Galvanized flexible steel conduit works from −50 °C to +300 °C and covers most general installations. Stainless steel conduit works from −100 °C to +600 °C and is made for corrosive environments. The choice comes down to temperature, chemicals and moisture.

Guide3 min read
PVC-coated vs halogen-free (LSZH) conduit
PVC-coated and halogen-free coated conduits protect the steel core from moisture, oil and dust in the same way; they differ in fire behaviour and temperature. A halogen-free (LSZH) coating gives off little smoke and no halogen gases in a fire, so it is chosen for crowded indoor spaces.

Guide3 min read
Liquid-tight conduit: where and why it is used
Liquid-tight conduit is galvanized flexible steel conduit enclosed in a thick PVC or halogen-free jacket, rated IP66–IP69. It is used wherever cables meet water, dust, petrol or solvents.

Technical3 min read
What does IP68 mean? IP ratings explained
In an IP code the first digit is protection against dust and solid objects, the second against water. IP68 means fully dust-tight and able to withstand continuous immersion.

Technical3 min read
PG vs metric gland threads: the difference and which to choose
PG and metric are two separate thread standards for cable glands, and they do not fit each other. New designs use metric threads; for existing enclosures with PG entries, choose a PG gland or an adapter.